DATAFLOW RTU
EXAMPLE 2
8.3 EXAMPLE 2 configures three DATAFLOW RTUs with one connected to two others. RTU
ID 1 has two digital inputs, two digital outputs and two analog outputs. RTU ID 2 and RTU
ID 3 each have one digital input, one digital output and one analog input. The inputs and
outputs are mapped to each other as shown in the following tables:
RTU ID 1 RF LINK 1 RTU ID 2
Input 1 connected to Digital Output 1
Input 2
Input 3
Input 4
Digital Output 1 connected to Input 1
Digital Output 2
Analog Output 1 connected to Input 2
Analog Output 2
RTU ID 1 RF LINK 2 RTU ID 3
Input 1
Input 2 connected to Digital Output 1
Input 3
Input 4
Digital Output 1
Digital Output 2 connected to Input 1
Analog Output 1
Analog Output 2 connected to Input 2
8.3.1 RTU ID 1 SETUP: Example 2 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B4 - EXAMPLE 2 RTU ID 1 Wiring Diagram, shown on page
B-28. Load Software Programming configuration file EXP2ID1.USR into RTU ID 1.
8.3.2 RTU ID 2 SETUP: Example 2 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B5 - EXAMPLE 2 RTU ID 2 Wiring Diagram, shown on page
B-29. Load Software Programming configuration file EXP2ID2.USR into RTU ID 2.
8.3.3 RTU ID 3 SETUP: Example 2 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B6 - EXAMPLE 2 RTU ID 3 Wiring Diagram, shown on page
B-30. Load Software Programming configuration file EXP2ID3.USR into RTU ID 3.
8.3.4 EXPLANATION: Example 2 illustrates point-to-multipoint RTU operation. Examine the
configuration files of these three RTUs. Be certain to understand the following items before
advancing to Example 3:
· SEND LIST
· FAIL-SAFE STATE
· I/O CONFIG
The following text provides detailed descriptions of the above items.
8.3.4.1 SEND LIST is the list of IDs used by the RTU when transmitting messages. Each outgoing
message has to ID n attached to it. In Example 2, RTU ID 1 has to ID 2 and to ID 3 in
its SEND LIST. RTU ID 1 transmit messages first to RTU ID 2. When an acknowledge is
received from RTU ID 2 or when the maximum number of attempts is reached, the
message is then transmitted to RTU ID 3.
(Example 2 continued on next page)
( B-17 )