DATAFLOW RTU
EXAMPLE 5
8.6 EXAMPLE 5 illustrates a DATAFLOW RTU system with one RTU configured as a repeater.
Connect the RTUs according to the following 2 tables:
RTU END 1 RF LINK 1 RTU END 2
Input 1 connected to Digital Output 1
Input 2
Input 3
Input 4
Digital Output 1
Digital Output 2
Analog Output 1 connected to Input 1
Analog Output 2
RTU END 1 RF LINK 2 RTU END 3
Input 1
Input 2 connected to Digital Output 1
Input 3
Input 4
Digital Output 1
Digital Output 2
Analog Output 1
Analog Output 2 connected to Input 1
NOTE: In Example 5:
· RTU ID 1 has line of sight with RTU ID 2, and RTU ID 2 has line of sight with RTU ID 3.
· RTU ID 1 DOES NOT HAVE line of sight with RTU ID 3.
· RTU ID 2 is configured as a repeater between RTU ID 1 and RTU ID 3.
8.6.1 RTU ID 1 SETUP: Example 5 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B9 - EXAMPLE 5 ID 1 Wiring Diagram on page B-33. Load
Software Programming configuration file EXP5ID1.USR into RTU ID 1.
8.6.2 RTU ID 2 SETUP: Example 5 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B10 - EXAMPLE 5 ID 2 Wiring Diagram on page B-34. Load
Software Programming configuration file EXP5ID2.USR into RTU ID 2.
8.6.3 RTU ID 3 SETUP: Example 5 requires one DATAFLOW RTU to be wired and its hardware
configured according to Figure B11 - EXAMPLE 5 ID 3 Wiring Diagram on page B-35. Load
Software Programming configuration file EXP5ID3.USR into RTU ID 3.
8.6.4 EXPLANATION: Using an RTU as a digital repeater can increase DATAFLOW RTU range.
This RTU performs both repeating and normal Input/ Output functions.
Examine the configurations of the three RTUs. Notice the fail-safe performance of each
unit.
· RTU ID 1  send list contains only ID 2.
· RTU ID 2  first line of the REPEAT LIST contains FROM ID 1 and TO ID 3; second
line of the REPEAT LIST contains FROM ID 3 and TO ID 1.
· RTU ID 3  send list contains only ID 2.
NOTE: You must extend the listen time of ID1 and ID3 to .8 seconds to allow for the repeat function.
( B-21 )